0.6/ 1kV PVC Insulated, Concentric Conductor Screen Single Core Cables with Aluminum Conductor

Code

YAVCV-R, AL/PVC/SC/PVC, NAYCY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations, and at local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. PVC inner sheath

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature   

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

 

1x25/16

16.0

400

1000

1.20

125

105

87

75

 

1x35/16

17.0

450

1000

0.868

151

127

131

113

 

1x50/25

19.5

630

1000

0.641

179

151

160

138

 

1x70/35

20.5

800

1000

0.443

218

186

202

174

 

1x95/50

24.0

1050

1000

0.320

261

223

249

210

 

1x120/70

26.0

1350

1000

0.253

297

254

291

244

 

1x150/70

27.5

1500

1000

0.206

332

285

333

281

 

1x185/95

30.0

1850

1000

0.164

376

323

384

320

 

1x240/120

33.5

2350

1000

0.125

437

378

460

378

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources