0.6/ 1kV PVC Insulated, Flat Steel Wire Armored Multi-Core Core Cables with Aluminum Conductor
Code YAVZ3V-R, NAYFGY R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603 |
Application Indoor and outdoor; in cable ducts;
in power or switching stations; at local energy distribution networks;
industrial plants where risk of mechanical damage exists. Construction 1. Stranded
aluminum conductors 2. PVC
insulation 3. Filler 4. Galvanized
flat steel wire 5. Galvanized
steel binding strap 6. PVC
outer jacket |
||||||||
Technical
Data |
|
|
|||||||
Max. operating temperature |
: |
70 oC |
|||||||
Max. short circuit
temperature |
: |
160 oC (Max. 5
sec.) |
|||||||
Rated voltage |
: |
0.6 / 1kV |
|||||||
Min. bending radius |
: |
15 x D |
|||||||
(D: Cable outer diameter) |
|||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|||
2x25 |
24.5 |
1100 |
1000 |
1.20 |
- |
83 |
|||
2x35 |
27.0 |
1300 |
1000 |
0.868 |
- |
102 |
|||
2x50 |
31.0 |
1700 |
1000 |
0.641 |
- |
124 |
|||
2x70 |
34.5 |
2050 |
1000 |
0.443 |
- |
158 |
|||
2x95 |
39.0 |
2600 |
1000 |
0.320 |
- |
190 |
|||
2x120 |
42.5 |
3050 |
1000 |
0.253 |
- |
221 |
|||
2x150 |
46.5 |
3600 |
1000 |
0.206 |
- |
252 |
|||
2x185 |
51.5 |
4350 |
1000 |
0.164 |
- |
289 |
|||
2x240 |
57.5 |
5350 |
500 |
0.125 |
- |
339 |
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In Air : 300C; load
factor 1.0
Number of System : 1