Product Detail

0.6/ 1kV PVC Insulated, Flat Steel Wire Armored Multi- Core Cables with Aluminum Conductor

Code

YAVZ3V-R, NAYFGY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exists.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. Galvanized flat steel wire

5. Galvanized steel binding strap

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

3x25

26.0

1250

1000

1.20

99

83

3x35

28.5

1500

1000

0.868

118

102

3x50

33.0

1900

1000

0.641

142

124

3x70

37.0

2350

1000

0.443

176

158

3x95

42.0

2950

1000

0.320

211

190

3x120

45.5

3500

1000

0.253

242

221

3x150

50.0

4200

1000

0.206

270

252

3x185

55.0

5000

500

0.164

308

289

3x240

61.5

6200

500

0.125

363

339

3x300

68.0

7450

500

0.100

412

377

3x400

76.5

9500

500

0.0778

475

444

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, PVC Insulated, FSW Armored, Multi Core (3) LV Cables.