Product Detail

0.6/ 1kV PVC Insulated, Flat Steel Wire Armored Multi- Core Cables with Aluminum Conductor

Code

YAVZ3V-R, NAYFGY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exists.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. Galvanized flat steel wire

5. Galvanized steel binding strap

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

4x25

28.5

1500

1000

1.20

99

83

4x35

31.0

1750

1000

0.868

118

102

4x50

36.5

2300

1000

0.641

142

124

4x70

40.5

2850

1000

0.443

176

158

4x95

46.0

3550

1000

0.320

211

190

4x120

50.0

4250

1000

0.253

242

221

4x150

55.5

5100

500

0.206

270

252

4x185

61.0

6100

500

0.164

308

289

4x240

68.0

7550

500

0.125

363

339

4x300

75.0

9100

500

0.100

412

377

4x400

85.0

11500

500

0.0778

475

444

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, PVC Insulated, FSW Armored, Multi Core (4) LV Cables.