Product Detail

0.6/ 1kV PVC Insulated, Multi-Core Cables with Aluminum Conductor

Code

YAVV-R, AL/PVC/PVC, NAYY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, and industrial plants where there is no risk of mechanical damage.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x16

20.0

500

1000

1.91

70

65

 

3x25

24.0

800

1000

1.20

99

83

 

3x35

26.0

950

1000

0.868

118

102

 

3x50

29.5

1220

1000

0.641

142

124

 

3x70

33.5

1640

1000

0.443

176

158

 

3x95

38.0

2140

1000

0.320

211

190

 

3x120

42.0

2500

1000

0.253

242

221

 

3x150

46.0

3100

1000

0.206

270

252

 

3x185

51.0

3800

500

0.164

308

289

 

3x240

58.0

4900

500

0.125

363

339

 

3x300

64.0

5900

500

0.100

412

377

 

3x400

71.0

7600

500

0.0778

475

444

 

 

 

 

 

 

 

 

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources