Product Detail

0.6/ 1kV PVC Insulated, Multi-Core Cables with Aluminum Conductor

Code

YAVV-R, AL/PVC/PVC, NAYY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, and industrial plants where there is no risk of mechanical damage.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x16+10

21.0

550

1000

1.91

70

65

 

3x25+16

25.0

900

1000

1.20

99

83

 

3x35+16

27.0

1000

1000

0.868

118

102

 

3x50+25

32.0

1400

1000

0.641

142

124

 

3x70+35

36.0

1800

1000

0.443

176

158

 

3x95+50

41.0

2400

1000

0.320

211

190

 

3x120+70

45.5

2900

1000

0.253

242

221

 

3x150+70

49.5

3450

1000

0.206

270

252

 

3x185+95

55.0

4250

500

0.164

308

289

 

3x240+120

61.5

5500

500

0.125

363

339

 

3x300+150

68.0

6550

500

0.100

412

377

 

3x400+185

76.5

8500

500

0.0778

475

444

 

 

 

 

 

 

 

 

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, PVC Insulated, Multi Core (3+1) LV Cables.