0.6/ 1kV PVC Insulated, Multi-Core Cables with Aluminum Conductor

Code

YAVV-R, AL/PVC/PVC, NAYY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, and industrial plants where there is no risk of mechanical damage.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

5x6

18.0

400

1000

4.87

-

-

5x10

21.0

550

1000

3.08

-

-

5x16

24.0

700

1000

1.91

70

65

5x25

29.0

1100

1000

1.20

99

83

5x35

31.0

1350

1000

0.868

118

102

5x50

36.0

1800

1000

0.641

142

124

5x70

41.0

2400

1000

0.443

176

158

5x95

48.0

3250

1000

0.320

211

190

5x120

52.0

3850

1000

0.253

242

221

5x150

57.0

4750

1000

0.206

270

252

5x185

63.0

5850

500

0.164

308

289

5x240

71.0

7400

500

0.125

363

339

5x300

78.0

9100

500

0.100

412

377

5x400

89.0

11550

500

0.0778

475

444

 

 

 

 

 

 

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1