0.6/ 1kV PVC Insulated, Round Aluminum Wire Armored Single Core Cables with Aluminum Conductor

Code

YAVY2V-R, AL/PVC/AWA/PVC, NAYR(A)Y

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS 6346

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exists.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. PVC inner sheath

4. Round aluminum wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

 

1x25

17.0

400

1000

1.20

125

105

87

75

 

1x35

18.0

450

1000

0.868

151

127

131

113

 

1x50

20.0

500

1000

0.641

179

151

160

138

 

1x70

21.5

650

1000

0.443

218

186

202

174

 

1x95

24.5

850

1000

0.320

261

223

249

210

 

1x120

26.0

950

1000

0.253

297

254

291

244

 

1x150

28.0

1100

1000

0.206

332

285

333

281

 

1x185

30.0

1300

1000

0.164

376

323

384

320

 

1x240

33.0

1550

1000

0.125

437

378

460

378

 

1x300

36.5

1950

1000

0.100

494

427

530

433

 

1x400

40.5

2350

1000

0.0778

572

496

642

523

 

1x500

44.0

2850

1000

0.0605

649

562

744

603

 

 

 

 

 

 

 

 

 

 

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, PVC Insulated, RAW Armored, Single Core LV Cables.