0.6/ 1kV PVC Insulated, Round Steel Wire Armored Multi- Core Cables with Aluminum Conductor

Code

YAVZ2V-R, AL/PVC/SWA/PVC, NAYRY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS 6346

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exists.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

3x25

27.0

1450

1000

1.20

99

83

3x35

29.5

1700

1000

0.868

118

102

3x50

34.0

2200

1000

0.641

142

124

3x70

39.0

2950

1000

0.443

176

158

3x95

44.0

3650

1000

0.320

211

190

3x120

47.5

4200

1000

0.253

242

221

3x150

53.0

5500

500

0.206

270

252

3x185

58.0

6350

500

0.164

308

289

3x240

64.5

7750

500

0.125

363

339

3x300

71.0

9150

500

0.100

412

377

3x400

81.5

12300

500

0.0778

475

444

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, PVC Insulated, RSW Armored, Multi Core (3) LV Cables.