Product Detail
0.6/ 1kV PVC Insulated, Round Steel Wire Armored Multi- Core Cables with Aluminum Conductor
Code YAVZ2V-R, AL/PVC/SWA/PVC, NAYRY R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603, BS 6346 |
Application Indoor, outdoor or underground;
in cable ducts; in power or switching stations; at local energy distribution
networks; industrial plants where risk of mechanical damage exists. Construction 1. Stranded aluminum conductors 2. PVC
insulation 3. Filler 4. Galvanized
round steel wire 5.
Polyester tape 6. PVC
outer jacket |
|||||||||
Technical
Data |
|
|
||||||||
Max. operating temperature |
: |
70 oC |
||||||||
Max. short circuit temperature |
: |
(Max. 5
sec.) |
||||||||
Cross section ≤ 300 mm2 |
: |
160 oC |
||||||||
Cross Section > 300 mm2 |
: |
140 oC |
||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||
Min. bending radius |
: |
15 x D |
||||||||
(D: Cable outer diameter) |
|
|
||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
|
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
|
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|
|||
4x25 |
29.5 |
1650 |
1000 |
1.20 |
99 |
83 |
|
|||
4x35 |
32.0 |
2000 |
1000 |
0.868 |
118 |
102 |
|
|||
4x50 |
38.5 |
2900 |
1000 |
0.641 |
142 |
124 |
|
|||
4x70 |
42.5 |
3450 |
1000 |
0.443 |
176 |
158 |
|
|||
4x95 |
49.0 |
4700 |
1000 |
0.320 |
211 |
190 |
|
|||
4x120 |
53.0 |
5500 |
1000 |
0.253 |
242 |
221 |
|
|||
4x150 |
58.5 |
6500 |
500 |
0.206 |
270 |
252 |
|
|||
4x185 |
64.0 |
7650 |
500 |
0.164 |
308 |
289 |
|
|||
4x240 |
71.0 |
9250 |
500 |
0.125 |
363 |
339 |
|
|||
4x300 |
78.0 |
10950 |
500 |
0.100 |
412 |
377 |
|
|||
4x400 |
89.5 |
14700 |
500 |
0.0778 |
475 |
444 |
|
|||
NOTE : Current carrying capacities
are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1