Product Detail

0.6/ 1kV PVC Insulated, Round Steel Wire Armored Multi- Core Cables with Aluminum Conductor

Code

YAVZ2V-R, AL/PVC/SWA/PVC, NAYRY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS 6346

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exists.

Construction

1. Stranded aluminum conductors

2. PVC insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

4x25

29.5

1650

1000

1.20

99

83

 

4x35

32.0

2000

1000

0.868

118

102

 

4x50

38.5

2900

1000

0.641

142

124

 

4x70

42.5

3450

1000

0.443

176

158

 

4x95

49.0

4700

1000

0.320

211

190

 

4x120

53.0

5500

1000

0.253

242

221

 

4x150

58.5

6500

500

0.206

270

252

 

4x185

64.0

7650

500

0.164

308

289

 

4x240

71.0

9250

500

0.125

363

339

 

4x300

78.0

10950

500

0.100

412

377

 

4x400

89.5

14700

500

0.0778

475

444

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, PVC Insulated, RSW Armored, Multi Core (4) LV Cables.