Product Detail

18/30 kV or 19/33 kV XLPE Insulated, Three Core Cables with Aluminum Conductor

Code

YAXC8V-R, NA2XSEY, AL/XLPE/CTS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

18/30 kV

 

 

19/33 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

68.0

5000

1000

0.868

0.457

0.114

-

-

3x50/16

71.5

5550

500

0.641

0.434

0.124

166

171

3x70/16

75.0

6200

500

0.443

0.410

0.137

204

211

3x95/16

79.0

6900

500

0.320

0.389

0.150

244

255

3x120/16

83.0

7650

500

0.253

0.372

0.163

278

297

3x150/25

86.0

8350

500

0.206

0.360

0.174

312

334

3x185/25

90.0

9200

500

0.164

0.348

0.188

343

384

3x240/25

97.0

10700

250

0.125

0.331

0.209

398

454

3x300/25

102.0

12000

250

0.100

0.321

0.226

-

-

3x400/35

110.0

14060

250

0.0778

0.307

0.251

-

-

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, 3-Core MV Cables (18/30 kV).