Product Detail

8.7/15 kV XLPE Insulated, Three Core Cables with Aluminum Conductor

Code

YAXC8V-R, NA2XSEY, AL/XLPE/CTS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

8.7/15 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

51.5

2950

1000

0.868

0.397

0.160

-

-

3x50/16

54.5

3400

1000

0.641

0.377

0.175

162

160

3x70/16

58.5

3900

1000

0.443

0.356

0.196

199

199

3x95/16

62.5

4500

1000

0.320

0.339

0.218

238

242

3x120/16

66.5

5100

500

0.253

0.325

0.240

271

280

3x150/25

69.5

5700

500

0.206

0.315

0.258

304

318

3x185/25

74.0

6500

500

0.164

0.305

0.280

345

365

3x240/25

80.0

7700

500

0.125

0.292

0.315

401

431

3x300/25

85.0

8800

500

0.100

0.284

0.343

453

494

3x400/35

93.0

10650

250

0.0778

0.273

0.385

517

569

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources