Product Detail
0.6/ 1kV XLPE Insulated, Concentric Conductor Screen Single Core Cables with Aluminum Conductor
Code YAXCV-R, AL/XLPE/SC/PVC, NA2XCY R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603 |
Application Characterized with low dielectric
loss. Indoor installations; in cable ducts; outdoor and underground at power
stations; in industrial plants and switching stations, and at local supply
systems where high degree of protection is required. In case of mechanical
damage, screen prevents hazardous effects of power leakage over surrounding
area. Construction 1. Stranded
aluminum conductors 2. XLPE
insulation 3. PVC
inner sheath 4.
Concentric copper wire 5. Copper
tape as binder 6.
Polyester tape 7. PVC outer
jacket |
||||||||||
Technical
Data |
|
|
|||||||||
Max. operating temperature |
: |
90 oC |
|||||||||
Max. short circuit
temperature |
: |
250 oC (Max. 5
sec.) |
|||||||||
Rated voltage |
: |
0.6 / 1kV |
|||||||||
Min. bending radius |
: |
15 x D |
|||||||||
(D: Cable outer diameter) |
|||||||||||
|
|||||||||||
|
|||||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
||||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity (A) |
||||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|||||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|||||
mm2 |
mm |
kg/km |
m |
Ohm/km |
*** |
*** |
*** |
*** |
|||
1x25/16 |
15.5 |
400 |
1000 |
1.20 |
- |
114 |
- |
106 |
|||
1x35/16 |
16.5 |
450 |
1000 |
0.868 |
164 |
137 |
163 |
131 |
|||
1x50/25 |
18.5 |
600 |
1000 |
0.641 |
195 |
163 |
200 |
161 |
|||
1x70/35 |
20.0 |
750 |
1000 |
0.443 |
238 |
201 |
254 |
205 |
|||
1x95/50 |
23.0 |
1000 |
1000 |
0.320 |
284 |
240 |
313 |
253 |
|||
1x120/70 |
25.0 |
1300 |
1000 |
0.253 |
323 |
274 |
366 |
296 |
|||
1x150/70 |
27.0 |
1400 |
1000 |
0.206 |
361 |
308 |
420 |
341 |
|||
1x185/95 |
29.5 |
1800 |
1000 |
0.164 |
408 |
350 |
486 |
395 |
|||
1x240/120 |
33.0 |
2200 |
1000 |
0.125 |
476 |
408 |
585 |
475 |
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
*** : Flat formation;
clearance between cables in air = 1 x cable outer diameter; in ground = 7cm
*** : Trefoil formation
Number of System : 1
Resources