Product Detail

0.6/ 1kV XLPE Insulated, Concentric Conductor Screen Single Core Cables with Aluminum Conductor

Code

YAXCV-R, AL/XLPE/SC/PVC, NA2XCY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Characterized with low dielectric loss. Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations, and at local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Stranded aluminum conductors

2. XLPE insulation

3. PVC inner sheath

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

1x25/16

15.5

400

1000

1.20

-

114

-

106

1x35/16

16.5

450

1000

0.868

164

137

163

131

1x50/25

18.5

600

1000

0.641

195

163

200

161

1x70/35

20.0

750

1000

0.443

238

201

254

205

1x95/50

23.0

1000

1000

0.320

284

240

313

253

1x120/70

25.0

1300

1000

0.253

323

274

366

296

1x150/70

27.0

1400

1000

0.206

361

308

420

341

1x185/95

29.5

1800

1000

0.164

408

350

486

395

1x240/120

33.0

2200

1000

0.125

476

408

585

475

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1