Product Detail

18/30 kV or 19/33 kV XLPE Insulated, Double Steel Tape Armored, Three Core Cables with Aluminum Conductor

Code

YAXC8VZ4V-R, NA2XSEYBY, AL/XLPE/CTS/PVC/STA/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. Inner sheath

9. Galvanized steel tape

10. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

18/30 kV

 

 

19/33 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

73.0

7334

500

0.868

0.457

0.114

-

-

3x50/16

75.9

7941

500

0.641

0.434

0.124

166

164

3x70/16

80.1

8819

500

0.443

0.410

0.137

204

204

3x95/16

85.3

10719

500

0.320

0.389

0.150

244

248

3x120/16

88.8

11597

250

0.253

0.372

0.163

278

284

3x150/25

92.2

12481

250

0.206

0.360

0.174

312

326

3x185/25

96.2

13600

250

0.164

0.348

0.188

343

374

3x240/25

102.4

15406

250

0.125

0.331

0.209

398

440

3x300/25

106.8

16833

250

0.100

0.321

0.226

-

-

3x400/25

114.5

19304

250

0.0778

0.307

0.251

-

-

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, DST Armored, 3-Core MV Cables (18/30 kV).