Product Detail

0.6/ 1kV XLPE Insulated, Double Steel Tape Armored Multi- Core Cables with Aluminum Conductor

Code

YAXZ4V-R, AL/XLPE/DSTA/PVC, NA2XBY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded aluminum conductors

2. XLPE insulation

3. Filler

4. Galvanized double steel tape

5. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

3x25

23.5

900

1000

1.20

111

100

3x35

26.0

1100

1000

0.868

132

122

3x50

30.0

1400

1000

0.641

157

147

3x70

34.5

1850

1000

0.443

195

189

3x95

38.5

2300

1000

0.320

233

232

3x120

43.0

3100

1000

0.253

266

270

3x150

48.5

3800

1000

0.206

299

308

3x185

53.0

4500

1000

0.164

340

357

3x240

59.0

5600

500

0.125

401

435

3x300

65.0

6700

500

0.100

455

501

3x400

73.5

8450

500

0.0778

526

592

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0