Product Detail

0.6/ 1kV XLPE Insulated, Double Steel Tape Armored Multi- Core Cables with Aluminum Conductor

Code

YAXZ4V-R, AL/XLPE/DSTA/PVC, NA2XBY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded aluminum conductors

2. XLPE insulation

3. Filler

4. Galvanized double steel tape

5. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

4x25

26.0

1050

1000

1.20

111

100

4x35

28.5

1300

1000

0.868

132

122

4x50

33.0

1550

1000

0.641

157

147

4x70

38.0

2250

1000

0.443

195

189

4x95

43.0

3100

1000

0.320

233

232

4x120

48.0

3800

1000

0.253

266

270

4x150

53.0

4550

1000

0.206

299

308

4x185

58.5

5450

500

0.164

340

357

4x240

65.5

6800

500

0.125

401

435

4x300

72.0

8100

500

0.100

455

501

4x400

82.0

10450

250

0.0778

526

592

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1 

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, DST Armored, Multi Core (4) LV Cables.