Product Detail

76/132 kV XLPE Insulated, Radial and Longitudinally Sealed, Single Core Cables with Aluminum Conductor

Code

NA2XS(FL)2Y, AL/XLPE/LW/CWS/LW/PE

Standards

VDE 0276-632, IEC 60840

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded aluminum conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Semi-conductive swelling tape

8. PE coated aluminum foil

9. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

76/132 kV

Min. bending radius

:

20 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Operation

Capacitance

(approx.)

DC Conductor

Resistance at

20 0C Max

Current Carrying Capacity (A)

mm2

mm

kg/km

µF/km

Ohm/km

In ground

at 20oC

In duct

at 20oC

In air at 30oC

***

***

1x300/25

74.0

5067

0.160

0.1000

337

360

546

510

1x400/35

77.0

5533

0.170

0.0778

453

411

690

626

1x500/35

80.0

6034

0.190

0.0605

510

450

770

615

1x630/35

84.0

6740

0.210

0.0469

566

512

907

842

1x800/35

90.0

7756

0.230

0.0367

638

586

1017

982

1x1000/50

94.0

8596

0.230

0.0291

718

647

1186

1098

1x1200/50

97.0

9319

0.250

0.0247

760

674

1260

1162

1x1600/70

104.0

10910

0.270

0.0212

923

841

1362

1221

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources