Product Detail

12/20 kV or 12.7/22 kV XLPE Insulated, Longitudinally Sealed Single Core Cables with Aluminum Conductor

Code

NA2XS(F)2Y, AL/XLPE/SCWBT/CWS/WBT/PE

Standards

IEC 60502-2, VDE 0276-620, BS 7870 - 4.10

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Swellable tape

8. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

12/20 kV

 

 

12.7/22 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

30.0

700

1000

0.868

1.1110

0.676

0.436

0.157

-

-

-

-

1x50/16

31.0

800

1000

0.641

0.8205

0.650

0.416

0.174

195

173

217

184

1x70/16

33.0

900

1000

0.443

0.5670

0.619

0.394

0.197

237

211

270

229

1x95/16

34.5

1000

1000

0.320

0.4096

0.595

0.377

0.218

282

252

328

278

1x120/16

36.5

1150

1000

0.253

0.3238

0.576

0.365

0.238

320

287

378

320

1x150/25

38.0

1350

1000

0.206

0.2637

0.559

0.353

0.258

353

320

425

363

1x185/25

40.0

1500

1000

0.164

0.2099

0.543

0.343

0.278

396

362

485

415

1x240/25

42.5

1700

1000

0.125

0.1600

0.523

0.330

0.308

457

421

573

493

1x300/35

44.5

1950

1000

0.100

0.1280

0.506

0.321

0.336

511

474

652

563

1x400/35

48.0

2400

1000

0.0778

0.1009

0.485

0.309

0.377

566

538

740

652

1x500/35

51.0

2800

1000

0.0605

0.0774

0.469

0.300

0.413

630

606

838

746

1x630/35

55.0

3250

1000

0.0469

0.0600

0.452

0.292

0.455

719

686

953

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, Longitudinally Sealed, Single Core MV Cables (12/20 kV).