Product Detail

18/30 kV or 19/33 kV XLPE Insulated, Longitudinally Sealed Single Core Cables with Aluminum Conductor

Code

NA2XS(F)2Y, AL/XLPE/SCWBT/CWS/WBT/PE

Standards

IEC 60502-2, VDE 0276-620, BS 7870 - 4.10

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Swellable tape

8. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

18/30 kV

 

 

19/33 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

35.0

900

1000

0.868

1.1110

0.686

0.467

0.123

-

-

-

-

1x50/16

36.5

1000

1000

0.641

0.8205

0.660

0.448

0.135

146

175

217

187

1x70/16

38.0

1150

1000

0.443

0.5670

0.629

0.423

0.151

238

214

270

232

1x95/16

40.0

1250

1000

0.320

0.4096

0.605

0.405

0.166

284

256

328

281

1x120/16

42.0

1400

1000

0.253

0.3238

0.586

0.391

0.180

322

290

378

323

1x150/25

43.5

1650

1000

0.206

0.2637

0.568

0.379

0.194

385

324

425

365

1x185/25

45.0

1800

1000

0.164

0.2099

0.552

0.367

0.208

400

366

485

418

1x240/25

48.0

2050

1000

0.125

0.1600

0.532

0.354

0.229

461

426

572

494

1x300/35

50.0

2300

1000

0.100

0.1280

0.515

0.343

0.248

516

479

649

564

1x400/35

53.5

2800

1000

0.0778

0.1009

0.494

0.330

0.276

572

545

737

654

1x500/35

56.5

3200

1000

0.0605

0.0774

0.478

0.320

0.301

638

614

835

747

1x630/35

60.5

3700

1000

0.0469

0.0600

0.461

0.310

0.330

728

690

950

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, Longitudinally Sealed, Single Core MV Cables (18/30 kV).