Product Detail

8.7/15 kV XLPE Insulated, Longitudinally Sealed Single Core Cables with Aluminum Conductor

Code

NA2XS(F)2Y, AL/XLPE/SCWBT/CWS/WBT/PE

Standards

IEC 60502-2, VDE 0276-620

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Swellable tape

8. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

8.7/15 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

28.0

650

1000

0.868

1.1110

0.672

0.422

0.181

-

-

-

-

1x50/16

29.0

700

1000

0.641

0.8205

0.646

0.403

0.201

194

171

215

181

1x70/16

30.5

800

1000

0.443

0.5670

0.615

0.381

0.229

236

209

269

226

1x95/16

32.5

900

1000

0.320

0.4096

0.591

0.364

0.255

281

249

327

275

1x120/16

34.5

1050

1000

0.253

0.3238

0.572

0.353

0.278

318

283

377

317

1x150/25

35.5

1250

1000

0.206

0.2637

0.555

0.341

0.302

350

316

424

359

1x185/25

37.5

1400

1000

0.164

0.2099

0.539

0.332

0.328

393

358

485

412

1x240/25

40.5

1600

1000

0.125

0.1600

0.519

0.321

0.363

453

416

573

489

1x300/35

42.5

1800

1000

0.100

0.1280

0.502

0.311

0.398

507

469

652

559

1x400/35

46.0

2300

1000

0.0778

0.1009

0.482

0.301

0.447

559

532

741

651

1x500/35

49.5

2650

1000

0.0605

0.0774

0.466

0.293

0.491

622

599

838

744

1x630/35

53.0

3100

1000

0.0469

0.0600

0.450

0.285

0.543

697

679

957

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, Longitudinally Sealed, Single Core MV Cables (8.7/15 kV).