Product Detail
0.6/ 1kV XLPE Insulated, Multi-Core Cables with Aluminum Conductor
Code YAXV-R, AL/XLPE/PVC, NA2XY R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603, BS 7889 |
Application Characterized with low
dielectric loss. Used indoor, outdoor or underground; in cable ducts; in
power or switching stations; at local energy distribution networks;
industrial plants where risk of mechanical damage exits. Construction 1. Stranded aluminum conductors 2. XLPE
insulation 3. Filler 4. PVC
outer jacket |
||||||||
Technical
Data |
|
|
|||||||
Max. operating temperature |
: |
90 oC |
|||||||
Max. short circuit temperature |
: |
250 oC (Max. 5 sec.) |
|||||||
Rated voltage |
: |
0.6 / 1kV |
|||||||
Min. bending radius |
: |
12 x D |
|||||||
(D: Cable outer diameter) |
|||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|||
3x25 |
22.5 |
650 |
1000 |
1.20 |
111 |
100 |
|||
3x35 |
25.0 |
800 |
1000 |
0.868 |
132 |
122 |
|||
3x50 |
28.5 |
1100 |
1000 |
0.641 |
157 |
147 |
|||
3x70 |
33.0 |
1500 |
1000 |
0.443 |
195 |
189 |
|||
3x95 |
37.0 |
1850 |
1000 |
0.320 |
233 |
232 |
|||
3x120 |
41.0 |
2300 |
1000 |
0.253 |
266 |
270 |
|||
3x150 |
46.0 |
2900 |
1000 |
0.206 |
299 |
308 |
|||
3x185 |
50.5 |
3500 |
1000 |
0.164 |
340 |
357 |
|||
3x240 |
57.0 |
4450 |
1000 |
0.125 |
401 |
435 |
|||
3x300 |
62.5 |
5450 |
500 |
0.100 |
455 |
501 |
|||
3x400 |
71.0 |
7100 |
500 |
0.0778 |
526 |
592 |
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources