0.6/ 1kV XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Aluminum Conductor

Code

YAXY2V-R, AL/XLPE/AWA/PVC, NA2XR(A)Y

R: Stranded Rigid Conductor

Standards

IEC 60502-1, BS 5467

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded aluminum conductors

2. XLPE insulation

3. PVC inner sheath

4. Round aluminum wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

1x25

15.5

300

1000

1.20

-

114

-

106

1x35

17.5

400

1000

0.868

164

137

163

131

1x50

19.5

450

1000

0.641

195

163

200

161

1x70

21.0

600

1000

0.443

238

201

254

205

1x95

23.5

750

1000

0.320

284

240

313

253

1x120

25.0

850

1000

0.253

323

274

366

296

1x150

27.0

1000

1000

0.206

361

308

420

341

1x185

29.5

1150

1000

0.164

408

350

486

395

1x240

32.0

1400

1000

0.125

476

408

585

475

1x300

35.5

1750

1000

0.100

537

462

675

548

1x400

39.5

2150

1000

0.0778

616

531

798

647

1x500

43.0

2600

1000

0.0605

699

601

926

749

 

 

 

 

 

 

 

 

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, RAW Armored, Single Core LV Cables.