Product Detail

18/30 kV or 19/33 kV XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Aluminum Conductor

Code

NA2XSYR(A)Y, AL/XLPE/CWS/PVC/AWA/PVC

Standards

IEC 60502 - 2, VDE 0276 - 620, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. Inner sheath

9. Round aluminum wire

10. Polyester tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

18/30 kV

 

 

19/33 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

-

-

100

0.8680

1.1110

-

-

-

-

-

-

-

1x50/16

39.9

1815

1000

0.6410

0.8205

0.632

0.351

0.135

196

175

217

187

1x70/16

41.8

1990

1000

0.4430

0.5670

0.601

0.332

0.151

238

214

270

202

1x95/16

43.5

2165

1000

0.3200

0.4096

0.577

0.318

0.166

284

256

328

281

1x120/16

46.4

2499

1000

0.2530

0.3238

0.558

0.308

0.180

322

290

378

323

1x150/25

48.0

2769

1000

0.2060

0.2637

0.541

0.299

0.194

355

324

425

365

1x185/25

49.6

2977

1000

0.1640

0.2099

0.525

0.292

0.208

400

366

485

418

1x240/25

52.4

3332

1000

0.1250

0.1600

0.506

0.284

0.229

461

426

572

494

1x300/35

54.6

3640

500

0.1000

0.1280

0.490

0.279

0.248

516

479

649

564

1x400/35

58.0

4235

500

0.0778

0.1009

0.471

0.275

0.276

572

545

737

454

1x500/35

61.2

4748

500

0.0605

0.0774

0.456

0.270

0.301

638

614

835

747

1x630/35

66.0

5480

500

0.0469

0.0600

0.440

0.264

0.330

728

690

950

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, RAW Armored, Single Core MV Cables (18/30 kV).