Product Detail

20.3/35 kV or 20.8/36 kV XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Aluminum Conductor

Code

NA2XSYR(A)Y, AL/XLPE/CWS/PVC/AWA/PVC

Standards

HD 620 S2, TSEK

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. Inner sheath

9. Round aluminum wire

10. Polyester tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

20.3/35 kV

 

 

20.8/36 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

42.0

1860

1000

0.868

1.1110

0.657

0.367

0.115

-

-

-

-

1x50/16

44.1

1980

1000

0.641

0.8205

0.632

0.351

0.125

196

175

217

187

1x70/16

45.8

2140

1000

0.443

0.5670

0.601

0.332

0.140

238

214

270

202

1x95/16

48.2

2510

1000

0.320

0.4096

0.577

0.318

0.153

284

256

328

281

1x120/16

50.5

2698

1000

0.253

0.3238

0.558

0.308

0.165

322

290

378

323

1x150/25

52.1

2940

1000

0.206

0.2637

0.541

0.299

0.178

355

324

425

365

1x185/25

54.2

3210

1000

0.164

0.2099

0.525

0.292

0.191

400

366

485

418

1x240/25

56.6

3555

1000

0.125

0.1600

0.506

0.284

0.209

461

426

572

494

1x300/35

58.5

3845

500

0.100

0.1280

0.490

0.279

0.226

516

479

649

564

1x400/35

62.3

4475

500

0.0778

0.1009

0.471

0.275

0.252

572

545

737

654

1x500/35

65.8

5035

500

0.0605

0.0774

0.456

0.270

0.274

638

614

835

747

1x630/35

68.0

5755

500

0.0469

0.0600

0.440

0.264

0.330

728

690

950

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, RAW Armored, Single Core MV Cables (20.3/35 kV).