Product Detail

3.6/6 kV XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Aluminum Conductor

Code

NA2XSYR(A)Y, AL/XLPE/CWS/PVC/AWA/PVC

Standards

IEC 60502 - 2, VDE 0276 - 620, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. Inner sheath

9. Round aluminum wire

10. Polyester tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

3.6/6 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

26.2

926

1000

0.868

1.1110

0.657

0.367

0.283

-

-

-

-

1x50/16

27.3

1000

1000

0.641

0.8205

0.632

0.351

0.315

186

178

233

188

1x70/16

29.0

1123

1000

0.443

0.5670

0.601

0.332

0.368

234

217

280

235

1x95/16

31.0

1270

1000

0.320

0.4096

0.577

0.318

0.414

287

259

344

286

1x120/16

32.3

1390

1000

0.253

0.3238

0.558

0.308

0.455

338

298

392

329

1x150/25

34.7

1705

1000

0.206

0.2637

0.541

0.299

0.499

388

333

441

376

1x185/25

36.6

1890

1000

0.164

0.2099

0.525

0.292

0.544

449

377

510

428

1x240/25

39.4

2177

1000

0.125

0.1600

0.506

0.284

0.587

530

438

587

508

1x300/35

41.8

2443

1000

0.100

0.1280

0.490

0.279

0.603

605

495

682

586

1x400/35

46.9

3159

500

0.0778

0.1009

0.471

0.275

0.642

678

562

781

676

1x500/35

50.6

3645

500

0.0605

0.0774

0.456

0.270

0.667

762

633

883

772

1x630/35

54.5

4291

500

0.0469

0.0600

0.440

0.264

0.739

858

712

1007

882

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, RAW Armored, Single Core MV Cables (3.6/6 kV).