Product Detail

5.8/10 kV (6/10 kV) XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Aluminum Conductor

Code

NA2XSYR(A)Y, AL/XLPE/CWS/PVC/AWA/PVC

Standards

IEC 60502 - 2, VDE 0276 - 620, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. Inner sheath

9. Round aluminum wire

10. Polyester tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

5.8/10 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

28.0

1015

1000

0.868

1.1110

0.657

0.367

0.223

-

-

-

-

1x50/16

29.3

1106

1000

0.641

0.8205

0.632

0.351

0.248

194

171

215

181

1x70/16

31.0

1230

1000

0.443

0.5670

0.601

0.332

0.285

236

209

269

226

1x95/16

32.9

1392

1000

0.320

0.4096

0.577

0.318

0.320

281

249

327

275

1x120/16

35.1

1600

1000

0.253

0.3238

0.558

0.308

0.350

318

283

377

317

1x150/25

36.7

1835

1000

0.206

0.2637

0.541

0.299

0.382

350

316

424

359

1x185/25

38.4

2013

1000

0.164

0.2099

0.525

0.292

0.415

393

358

485

412

1x240/25

41.0

2286

1000

0.125

0.1600

0.506

0.284

0.462

453

416

573

489

1x300/35

43.2

2556

1000

0.100

0.1280

0.490

0.279

0.507

507

469

652

559

1x400/35

47.7

3227

500

0.0778

0.1009

0.471

0.275

0.573

559

532

741

651

1x500/35

51.0

3674

500

0.0605

0.0774

0.456

0.270

0.631

622

599

838

744

1x630/35

55.0

4365

500

0.0469

0.0600

0.440

0.264

0.699

697

679

957

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, RAW Armored, Single Core MV Cables (5.8/10 kV).