Product Detail

0.6/ 1kV XLPE Insulated, Round Steel Wire Armored Multi- Core Cables with Aluminum Conductor

Code

YAXY2V-R, AL/XLPE/SWA/PVC, NA2XRY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, BS 5467

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded aluminum conductors

2. XLPE insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

4x25

28.0

1500

1000

1.20

111

100

4x35

31.0

1800

1000

0.868

132

122

4x50

35.0

2300

1000

0.641

157

147

4x70

41.0

3200

1000

0.443

195

189

4x95

45.5

3850

1000

0.320

233

232

4x120

51.5

5100

500

0.253

266

270

4x150

56.5

6000

500

0.206

299

308

4x185

62.0

7000

500

0.164

340

357

4x240

68.5

8500

500

0.125

401

435

4x300

75.0

10000

500

0.100

455

501

4x400

86.5

13650

250

0.0778

526

592

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, RSW Armored, Multi Core (4) LV Cables.