0.6/ 1kV XLPE Insulated, Single Core Cables with Aluminum Conductor 

Code

YAXV-R, AL/XLPE/PVC, NA2XY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS 7889

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded aluminum conductors

2. XLPE insulation

3. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

1x25

10.5

150

1000

1.20

-

114

-

106

1x35

12.0

180

1000

0.868

164

137

163

131

1x50

13.5

250

1000

0.641

195

163

200

161

1x70

15.5

300

1000

0.443

238

201

254

205

1x95

17.0

400

1000

0.320

284

240

313

253

1x120

19.0

500

1000

0.253

323

274

366

296

1x150

21.0

600

1000

0.206

361

308

420

341

1x185

23.0

750

1000

0.164

408

348

486

395

1x240

26.0

950

1000

0.125

476

408

585

475

1x300

27.0

1150

1000

0.100

537

462

675

548

1x400

31.0

1450

1000

0.0778

616

531

798

647

1x500

35.0

1800

1000

0.0605

699

601

926

749

 

 

 

 

 

 

 

 

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1