Product Detail

3.6/6 kV XLPE Insulated, Single Core Cables with Aluminum Conductor

Code

YAXC7V-R, NA2XSY, AL/XLPE/CWS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620

 

Application

Characterized with low dielectric loss. Used indoors outdoors, and underground, in cable ducts, at power or switching stations, local energy networks, industrial plans where there is no risk of mechanical damage.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

3.6 /6 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

21.0

550

1000

0.868

1.1110

0.657

0.367

0.283

-

-

-

-

1x50/16

22.0

600

1000

0.641

0.8205

0.632

0.351

0.318

186

178

233

188

1x70/16

24.0

700

1000

0.443

0.5670

0.601

0.332

0.368

234

217

280

235

1x95/16

25.5

800

1000

0.320

0.4096

0.577

0.318

0.414

287

259

344

286

1x120/16

27.0

900

1000

0.253

0.3238

0.558

0.308

0.455

338

298

392

329

1x150/25

28.5

1100

1000

0.206

0.2637

0.541

0.299

0.499

388

333

441

376

1x185/25

30.5

1250

1000

0.164

0.2099

0.525

0.292

0.544

449

377

510

428

1x240/25

33.5

1450

1000

0.125

0.1600

0.506

0.284

0.587

530

438

587

508

1x300/35

36.0

1700

1000

0.100

0.1280

0.490

0.279

0.603

605

495

682

586

1x400/35

40.0

2200

1000

0.0778

0.1009

0.471

0.275

0.642

678

562

781

676

1x500/35

43.5

2600

1000

0.0605

0.0774

0.456

0.270

0.667

762

633

883

772

1x630/35

47.0

3050

1000

0.0469

0.0600

0.440

0.264

0.739

858

712

1007

882

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Al Conductor, XLPE Insulated, Single Core MV Cables (3.6/6 kV).