Product Detail
0.6/ 1kV PVC Insulated, Concentric Conductor Screen, Control Cables with Copper Conductor
Code YVCV-U, YVCV-R, CU/PVC/SC/PVC, NYCY U: Solid Conductor R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0271 |
Application Indoor installations; in cable ducts;
outdoor and underground at power stations; in industrial plants and switching
stations as well as local supply systems where high degree of protection is
required. In case of mechanical damage, screen prevents hazardous effects of
power leakage over surrounding area. Construction 1. Solid
or stranded copper conductors 2. PVC
insulation 3. Filler 4.
Concentric copper wire 5. Copper
tape as binder 6.
Polyester tape 7. PVC
outer jacket |
|||||||||
Technical
Data |
|
|
||||||||
Max. operating temperature |
: |
70 oC |
||||||||
Max. short circuit temperature |
: |
160 oC (Max. 5 sec.) |
||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||
Min. bending radius |
: |
15 x D |
||||||||
(D: Cable outer diameter) |
||||||||||
|
||||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
|
||||||||
Nominal |
Overall |
|
|
DC Conductor |
Current
Carrying Capacity |
|
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|
|||
7x1,5/2,5 |
16.0 |
350 |
1000 |
12.1 |
15.6 |
12.0 |
|
|||
8x1,5/2,5 |
18.2 |
400 |
1000 |
12.1 |
14.3 |
11.1 |
|
|||
10x1.5/2.5 |
19.0 |
500 |
1000 |
12.1 |
13.0 |
10.2 |
|
|||
12x1.5/2.5 |
19.5 |
550 |
1000 |
12.1 |
12.3 |
9.7 |
|
|||
14x1.5/2.5 |
20.0 |
600 |
1000 |
12.1 |
11.7 |
9.3 |
|
|||
19x1.5/4 |
22.0 |
750 |
1000 |
12.1 |
10.4 |
8.3 |
|
|||
24x1.5/6 |
25.0 |
1000 |
1000 |
12.1 |
9.1 |
7.4 |
|
|||
27x1.5/6 |
26.0 |
1000 |
1000 |
12.1 |
8.8 |
7.2 |
|
|||
30x1.5/6 |
26.5 |
1100 |
1000 |
12.1 |
8.6 |
7.0 |
|
|||
37x1.5/10 |
28.0 |
1350 |
1000 |
12.1 |
8.1 |
6.7 |
|
|||
7x2,5/2,5 |
17.5 |
450 |
1000 |
7.41 |
20.4 |
16.3 |
|
|||
8x2,5/2,5 |
20.5 |
550 |
1000 |
7.41 |
18.7 |
15.0 |
|
|||
10x2.5/4 |
21.0 |
650 |
1000 |
7.41 |
17.0 |
13.8 |
|
|||
12x2.5/4 |
22.0 |
700 |
1000 |
7.41 |
16.2 |
13.1 |
|
|||
14x2.5/2.5 |
22.3 |
800 |
1000 |
7.41 |
15.3 |
12.5 |
|
|||
19x2.5/6 |
24.3 |
1000 |
1000 |
7.41 |
13.6 |
11.3 |
|
|||
24x2.5/10 |
28.5 |
1350 |
1000 |
7.41 |
11.9 |
10.0 |
|
|||
27x2.5/10 |
28.0 |
1470 |
1000 |
7.41 |
11.5 |
9.8 |
|
|||
30x2.5/10 |
29.0 |
1550 |
1000 |
7.41 |
11.2 |
9.4 |
|
|||
37x2.5/10 |
31.0 |
1800 |
1000 |
7.41 |
10.6 |
9.1 |
|
|||
7x4/4 |
20.0 |
650 |
1000 |
4.61 |
26.4 |
22.1 |
|
|||
8x4/6 |
23.0 |
800 |
1000 |
4.61 |
24.2 |
20.4 |
|
|||
10x4/6 |
24.5 |
950 |
1000 |
4.61 |
22.0 |
18.7 |
|
|||
12x4/6 |
25.0 |
1050 |
1000 |
4.61 |
20.9 |
17.9 |
|
|||
14x4/6 |
25.5 |
1200 |
1000 |
4.61 |
19.8 |
17.0 |
|
|||
19x4/10 |
28.0 |
1500 |
1000 |
4.61 |
17.6 |
15.3 |
|
|||
|
|
|
|
|
|
|
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, PVC Insulated, CC Screen Control Cables (1).