Product Detail

0.6/ 1kV PVC Insulated, Concentric Conductor Screen, Control Cables with Copper Conductor

Code

YVCV-U, CU/PVC/SC/PVC, NYCY

U: Solid Conductor

Standards

IEC 60502-1, VDE 0271

Application

Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations as well as local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Solid copper conductors

2. PVC insulation

3. Filler

4. Concentric copper wire

5. Copper tape as binder (100% overlap)

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

7x1,5/9

16.0

410

1000

12.1

15.6

12.0

 

8x1,5/9

17.0

460

1000

12.1

14.3

11.1

 

10x1.5/9

19.0

560

1000

12.1

13.0

10.2

 

12x1.5/9

19.5

610

1000

12.1

12.3

9.7

 

14x1.5/9

20.0

660

1000

12.1

11.7

9.3

 

19x1.5/9

22.0

900

1000

12.1

10.4

8.3

 

24x1.5/9

25.0

1060

1000

12.1

9.1

7.4

 

27x1.5/9

25.5

1120

1000

12.1

8.8

7.2

 

30x1.5/9

26.0

1160

1000

12.1

8.6

7.0

 

37x1.5/9

28.0

1410

1000

12.1

8.1

6.7

 

7x2,5/9

17.0

510

1000

7.41

20.4

16.3

 

8x2,5/9

18.5

610

1000

7.41

18.7

15.0

 

10x2.5/9

20.5

720

1000

7.41

17.0

13.8

 

12x2.5/9

21.0

760

1000

7.41

16.2

13.1

 

14x2.5/9

22.0

860

1000

7.41

15.3

12.5

 

19x2.5/9

24.0

1060

1000

7.41

13.6

11.3

 

24x2.5/9

27.0

1410

1000

7.41

11.9

10.0

 

27x2.5/9

28.0

1455

1000

7.41

11.5

9.8

 

30x2.5/9

28.5

1610

1000

7.41

11.2

9.4

 

37x2.5/9

30.5

1860

1000

7.41

10.6

9.1

 

7x4/9

19.5

710

1000

4.61

26.4

22.1

 

8x4/9

21.5

860

1000

4.61

24.2

20.4

 

10x4/9

24.0

1010

1000

4.61

22.0

18.7

 

12x4/9

24.5

1110

1000

4.61

20.9

17.9

 

14x4/9

25.5

1280

1000

4.61

19.8

17.0

 

19x4/9

28.0

1560

1000

4.61

17.6

15.3

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources