Product Detail

0.6/ 1kV PVC Insulated, Concentric Conductor Screen, Multi-Core Cables with Copper Conductor

Code

YVCV-U, YVCV-R, CU/PVC/SC/PVC, NYCY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations as well as local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

2x1,5/1,5

13.0

240

1000

12.1

32

20

 

2x2,5/2,5

13.5

250

1000

7.41

42

27

 

2x4/4

15.5

280

1000

4.61

54

37

 

2x6/6

16.5

420

1000

3.08

68

48

 

2x10/10

19.0

600

1000

1.83

90

66

 

2x16/16

21.0

850

1000

1.15

116

89

 

2x25/16

24.0

1150

1000

0.727

150

118

 

2x35/16

26.0

1400

1000

0.524

181

145

 

2x50/25

29.0

1900

1000

0.387

215

176

 

2x70/35

32.5

2550

1000

0.268

264

224

 

2x95/50

37.5

3450

1000

0.193

317

271

 

2x120/70

41.5

4300

1000

0.153

360

314

 

2x150/70

45.0

5100

500

0.124

406

361

 

2x185/95

50.5

6450

500

0.0991

458

412

 

2x240/120

57.0

8300

500

0.0754

537

484

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, CC Screen, Multi Core (2) LV Cables.