Product Detail

0.6/ 1kV PVC Insulated, Concentric Conductor Screen, Multi-Core Cables with Copper Conductor

Code

YVCV-U, YVCV-R, CU/PVC/SC/PVC, NYCY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations as well as local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

4x1,5/1,5

14.5

290

1000

12.1

26

18.5

 

4x2,5/2,5

15.5

350

1000

7.41

34

25

 

4x4/4

17.5

490

1000

4.61

44

34

 

4x6/6

18.5

600

1000

3.08

56

43

 

4x10/10

22.0

890

1000

1.83

75

60

 

4x16/16

24.0

1200

1000

1.15

98

80

 

4x25/16

28.0

1750

1000

0.727

128

106

 

4x35/16

30.0

2200

1000

0.524

157

131

 

4x50/25

34.0

3000

1000

0.387

185

159

 

4x70/35

39.0

4050

1000

0.268

228

202

 

4x95/50

46.0

5500

500

0.193

275

244

 

4x120/70

50.0

6900

500

0.153

313

282

 

4x150/70

54.0

8300

500

0.124

353

324

 

4x185/95

61.0

10400

250

0.0991

399

371

 

4x240/120

69.0

13300

250

0.0754

464

436

 

4x300/150

74.0

16300

250

0.0601

524

481

 

4x400/185

83.0

20500

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0