Product Detail

0.6/ 1kV PVC Insulated, Concentric Conductor Screen, Single Core Cables with Copper Conductor

Code

YVCV-U, YVCV-R, CU/PVC/SC/PVC, NYCY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations as well as local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. PVC inner sheath

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

 

1x1,5/1,5

10.5

145

1000

12.1

-

30

25

20

 

1x2,5/2,5

11.0

150

1000

7.41

-

39

34

27

 

1x4/4

12.0

200

1000

4.61

-

50

45

37

 

1x6/6

12.5

250

1000

3.08

-

62

57

48

 

1x10/10

13.5

350

1000

1.83

-

83

78

66

 

1x16/16

15.0

450

1000

1.15

127

107

103

89

 

1x25/16

16.5

600

1000

0.727

163

137

137

118

 

1x35/16

17.5

700

1000

0.524

195

165

169

145

 

1x50/25

19.0

950

1000

0.387

230

195

206

176

 

1x70/35

21.0

1250

1000

0.268

282

239

261

224

 

1x95/50

23.5

1650

1000

0.193

336

287

321

271

 

1x120/70

25.5

2100

1000

0.153

382

326

374

314

 

1x150/70

27.0

2400

1000

0.124

428

366

428

361

 

1x185/95

30.0

3000

1000

0.0991

483

414

494

412

 

1x240/120

33.5

3850

1000

0.0754

561

481

590

484

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, CC Screen, Single Core LV Cables.