Product Detail

0.6/ 1kV PVC Insulated, Control Cables with Copper Conductor

Code

YVV-U, YVV-R, CU/PVC/PVC, NYY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0271

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

5x2,5

13.5

320

1000

7.41

23.8

18.8

6x2,5

14.5

375

1000

7.41

22.1

17.5

7x2,5

14.5

415

1000

7.41

20.4

16.3

8x2,5

17.0

500

1000

7.41

18.7

15.0

10x2,5

18.0

595

1000

7.41

17.0

13.8

12x2,5

18.5

650

1000

7.41

16.2

13.1

14x2,5

19.5

730

1000

7.41

15.3

12.5

16x2,5

20.5

825

1000

7.41

14.5

11.9

19x2,5

21.5

920

1000

7.41

13.6

11.3

21x2,5

22.5

1010

1000

7.41

12.9

10.8

24x2,5

24.8

1190

1000

7.41

11.9

10.0

27x2,5

25.3

1280

1000

7.41

11.6

9.7

30x2,5

27.0

1380

1000

7.41

11.2

9.4

37x2,5

29.5

1660

1000

7.41

10.6

9.1

40x2,5

30.5

1800

1000

7.41

10.2

8.8

48x2,5

32.5

2135

1000

7.41

9.5

8.3

52x2,5

34.5

2320

1000

7.41

8.9

7.8

61x2,5

37.0

2630

1000

7.41

8.5

7.5

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated Control Cables (2).