Product Detail

0.6/ 1kV PVC Insulated, Double Steel Tape Armored Multi-Core Cables with Copper Conductor

Code

YVZ4V-U, YVZ4V-R, CU/PVC/DSTA/PVC, NYBY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS6346

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Galvanized double steel tape

5. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x1.5

13.0

320

1000

12.1

26

18.5

 

3x2.5

14.0

380

1000

7.41

34

25

 

3x4

16.0

500

1000

4.61

44

34

 

3x6

17.0

600

1000

3.08

56

43

 

3x10

19.5

800

1000

1.83

75

60

 

3x16

21.5

1050

1000

1.15

98

80

 

3x25

25.0

1500

1000

0.727

128

106

 

3x35

27.0

1850

1000

0.524

157

131

 

3x50

31.0

2450

1000

0.387

185

159

 

3x70

35.0

3300

1000

0.268

228

202

 

3x95

40.5

4650

1000

0.193

275

244

 

3x120

44.0

5600

500

0.153

313

282

 

3x150

48.5

6800

500

0.124

353

324

 

3x185

53.5

8300

500

0.0991

399

371

 

3x240

60.5

10600

250

0.0754

464

436

 

3x300

68.0

13000

250

0.0601

524

481

 

3x400

77.0

17000

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, DST Armored, Multi Core (3) LV Cables.