Product Detail
0.6/ 1kV PVC Insulated, Double Steel Tape Armored Multi-Core Cables with Copper Conductor
Code YVZ4V-U, YVZ4V-R, CU/PVC/DSTA/PVC, NYBY U: Solid Conductor R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603, BS6346 |
Application Indoor, outdoor or
underground; in cable ducts; in power or switching stations; at local energy
distribution networks; industrial plants where risk of mechanical damage
exits. Construction 1. Solid or stranded copper conductors 2. PVC insulation 3. Filler 4.
Galvanized double steel tape 5. PVC
outer jacket |
|||||||||
Technical
Data |
|
|
||||||||
Max. operating temperature |
: |
70 oC |
||||||||
Max. short circuit temperature |
: |
(Max. 5
sec.) |
||||||||
Cross section ≤ 300 mm2 |
: |
160 oC |
||||||||
Cross Section >
300 mm2 |
: |
140 oC |
||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||
Min. bending radius |
: |
15 x D |
||||||||
(D: Cable outer diameter) |
||||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
|
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
|
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In Ground
at |
In Air
at |
|
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|
|||
4x1.5 |
14.0 |
360 |
1000 |
12.1 |
26 |
18.5 |
|
|||
4x2.5 |
15.0 |
440 |
1000 |
7.41 |
34 |
25 |
|
|||
4x4 |
17.0 |
580 |
1000 |
4.61 |
44 |
34 |
|
|||
4x6 |
18.0 |
700 |
1000 |
3.08 |
56 |
43 |
|
|||
4x10 |
21.0 |
980 |
1000 |
1.83 |
75 |
60 |
|
|||
4x16 |
23.5 |
1300 |
1000 |
1.15 |
98 |
80 |
|
|||
4x25 |
27.0 |
1850 |
1000 |
0.727 |
128 |
106 |
|
|||
4x35 |
29.5 |
2350 |
1000 |
0.524 |
157 |
131 |
|
|||
4x50 |
34.0 |
3100 |
1000 |
0.387 |
185 |
159 |
|
|||
4x70 |
39.0 |
4450 |
1000 |
0.268 |
228 |
202 |
|
|||
4x95 |
44.5 |
5800 |
500 |
0.193 |
275 |
244 |
|
|||
4x120 |
49.0 |
7100 |
500 |
0.153 |
313 |
282 |
|
|||
4x150 |
53.5 |
8600 |
500 |
0.124 |
353 |
324 |
|
|||
4x185 |
59.0 |
10500 |
250 |
0.0991 |
399 |
371 |
|
|||
4x240 |
67.0 |
13400 |
250 |
0.0754 |
464 |
436 |
|
|||
4x300 |
75.5 |
16600 |
250 |
0.0601 |
524 |
481 |
|
|||
4x400 |
85.5 |
21650 |
250 |
0.0470 |
600 |
560 |
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources