Product Detail

0.6/ 1kV PVC Insulated, Double Steel Tape Armored Multi-Core Cables with Copper Conductor

Code

YVZ4V-U, YVZ4V-R, CU/PVC/DSTA/PVC, NYBY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS6346

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Galvanized double steel tape

5. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

4x1.5

14.0

360

1000

12.1

26

18.5

 

4x2.5

15.0

440

1000

7.41

34

25

 

4x4

17.0

580

1000

4.61

44

34

 

4x6

18.0

700

1000

3.08

56

43

 

4x10

21.0

980

1000

1.83

75

60

 

4x16

23.5

1300

1000

1.15

98

80

 

4x25

27.0

1850

1000

0.727

128

106

 

4x35

29.5

2350

1000

0.524

157

131

 

4x50

34.0

3100

1000

0.387

185

159

 

4x70

39.0

4450

1000

0.268

228

202

 

4x95

44.5

5800

500

0.193

275

244

 

4x120

49.0

7100

500

0.153

313

282

 

4x150

53.5

8600

500

0.124

353

324

 

4x185

59.0

10500

250

0.0991

399

371

 

4x240

67.0

13400

250

0.0754

464

436

 

4x300

75.5

16600

250

0.0601

524

481

 

4x400

85.5

21650

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, DST Armored, Multi Core (4) LV Cables.