Product Detail

0.6/ 1kV PVC Insulated, Multi Core Cables with Copper Conductor

Code

YVV-U, YVV-R, CU/PVC/PVC, NYY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x1,5

11.0

200

1000

12.1

26

18.5

 

3x2,5

11.8

230

1000

7.41

34

25

 

3x4

13.6

340

1000

4.61

44

34

 

3x6

15.5

425

1000

3.08

56

43

 

3x10

17.5

620

1000

1.83

75

60

 

3x16

19.5

835

1000

1.15

98

80

 

3x25

24.0

1250

1000

0.727

128

106

 

3x35

26.0

1600

1000

0.524

157

131

 

3x50

29.5

2100

1000

0.387

185

159

 

3x70

33.5

2900

1000

0.268

228

202

 

3x95

38.0

3900

1000

0.193

275

244

 

3x120

42.0

4800

1000

0.153

313

282

 

3x150

46.0

5900

500

0.124

353

324

 

3x185

51.0

7300

500

0.0991

399

371

 

3x240

58.0

9450

500

0.0754

464

436

 

3x300

65.0

11800

250

0.0601

524

481

 

3x400

71.0

15500

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, Multi Core (3) LV Cables.