Product Detail

0.6/ 1kV PVC Insulated, Multi Core Cables with Copper Conductor

Code

YVV-U, YVV-R, CU/PVC/PVC, NYY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

4x1,5

11.6

235

1000

12.1

26

18.5

 

4x2,5

12.6

270

1000

7.41

34

25

 

4x4

14.8

400

1000

4.61

44

34

 

4x6

16.0

520

1000

3.08

56

43

 

4x10

18.0

690

1000

1.83

75

60

 

4x16

21.5

1050

1000

1.15

98

80

 

4x25

26.0

1550

1000

0.727

128

106

 

4x35

28.5

2000

1000

0.524

157

131

 

4x50

33.0

2750

1000

0.387

185

159

 

4x70

37.5

3750

1000

0.268

228

202

 

4x95

42.5

5000

1000

0.193

275

244

 

4x120

46.5

6200

500

0.153

313

282

 

4x150

51.5

7600

500

0.124

353

324

 

4x185

57.0

9450

500

0.0991

399

371

 

4x240

65.0

12200

500

0.0754

464

436

 

4x300

73.0

15200

250

0.0601

524

481

 

4x400

79.0

19500

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, Multi Core (4) LV Cables.