Product Detail
0.6/ 1kV PVC Insulated, Round Steel Wire Armored Control Cables with Copper Conductor
Code YVZ2V-U, YVZ2V-R, CU/PVC/SWA/PVC,
NYRY U: Solid Conductor R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0271, BS6346 |
Application Indoor, outdoor or
underground; in cable ducts; in power or switching stations; at local energy
distribution networks; industrial plants where risk of mechanical damage
exits. Construction 1. Solid or stranded copper conductors 2. PVC
insulation 3. Filler 4.
Galvanized round steel wire 5.
Polyester tape 6. PVC
outer jacket |
||||||||
Technical
Data |
|
|
|||||||
Max. operating temperature |
: |
70 oC |
|||||||
Max. short circuit temperature |
: |
160 oC (Max. 5 sec.) |
|||||||
Rated voltage |
: |
0.6 / 1kV |
|||||||
Min. bending radius |
: |
15 x D |
|||||||
(D: Cable outer diameter) |
|||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|||
5x1,5 |
15.5 |
460 |
1000 |
12.1 |
18.2 |
14.0 |
|||
6x1,5 |
16.5 |
520 |
1000 |
12.1 |
16.9 |
13.0 |
|||
7x1,5 |
16.5 |
530 |
1000 |
12.1 |
15.6 |
12.0 |
|||
8x1,5 |
18.5 |
820 |
1000 |
12.1 |
14.3 |
11.1 |
|||
10x1,5 |
20.5 |
870 |
1000 |
12.1 |
13.0 |
10.2 |
|||
12x1,5 |
21.0 |
920 |
1000 |
12.1 |
12.3 |
9.7 |
|||
14x1,5 |
21.5 |
1000 |
1000 |
12.1 |
11.7 |
9.3 |
|||
16x1,5 |
22.5 |
1100 |
1000 |
12.1 |
11.1 |
8.8 |
|||
19x1,5 |
24.0 |
1300 |
1000 |
12.1 |
10.4 |
8.3 |
|||
21x1,5 |
25.0 |
1400 |
1000 |
12.1 |
9.9 |
8.0 |
|||
24x1,5 |
27.0 |
1600 |
1000 |
12.1 |
9.1 |
7.4 |
|||
27x1,5 |
27.5 |
1700 |
1000 |
12.1 |
8.8 |
7.2 |
|||
30x1,5 |
28.0 |
1800 |
1000 |
12.1 |
8.6 |
7.0 |
|||
37x1,5 |
30.0 |
2050 |
1000 |
12.1 |
8.1 |
6.7 |
|||
40x1,5 |
31.0 |
2150 |
1000 |
12.1 |
7.8 |
6.5 |
|||
48x1,5 |
34.5 |
2750 |
1000 |
12.1 |
7.3 |
6.1 |
|||
52x1,5 |
36.0 |
2950 |
1000 |
12.1 |
6.7 |
5.8 |
|||
61x1,5 |
37.5 |
3250 |
1000 |
12.1 |
6.5 |
5.6 |
|||
|
|
|
|
|
|
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, PVC Insulated, RSW Armored Control Cables (1).