Product Detail

0.6/ 1kV PVC Insulated, Round Steel Wire Armored Control Cables with Copper Conductor

Code

YVZ2V-U, YVZ2V-R, CU/PVC/SWA/PVC, NYRY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0271

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

5x2,5

16.5

550

1000

7.41

23.8

18.8

6x2,5

18.5

750

1000

7.41

22.1

17.5

7x2,5

18.0

760

1000

7.41

20.4

16.3

8x2,5

20.0

880

1000

7.41

18.7

15.0

10x2,5

22.0

1050

1000

7.41

17.0

13.8

12x2,5

22.5

1100

1000

7.41

16.2

13.1

14x2,5

24.0

1350

1000

7.41

15.3

12.5

16x2,5

25.0

1500

1000

7.41

14.5

11.9

19x2,5

26.0

1600

1000

7.41

13.6

11.3

21x2,5

27.0

1750

1000

7.41

12.9

10.8

24x2,5

29.5

2000

1000

7.41

11.9

10.0

27x2,5

30.0

2100

1000

7.41

11.6

9.7

30x2,5

31.0

2250

1000

7.41

11.2

9.4

37x2,5

33.0

2600

1000

7.41

10.6

9.1

40x2,5

35.0

2800

1000

7.41

10.2

8.8

48x2,5

38.5

3550

1000

7.41

9.5

8.3

52x2,5

39.5

3700

1000

7.41

8.9

7.8

61x2,5

41.5

4150

1000

7.41

8.5

7.5

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1