Product Detail

0.6/ 1kV PVC Insulated, Round Steel Wire Armored, Multi-Core Cables with Copper Conductor

Code

YVZ2V-U, YVZ2V-R, CU/PVC/SWA/PVC, NYRY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS6346

Application

Indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section ≤ 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

4x1,5

15.0

400

1000

12.1

26

18.5

 

4x2,5

15.5

480

1000

7.41

34

25

 

4x4

18.5

770

1000

4.61

44

34

 

4x6

20.0

900

1000

3.08

56

43

 

4x10

23.0

1200

1000

1.83

75

60

 

4x16

26.0

1700

1000

1.15

98

80

 

4x25

29.5

2300

1000

0.727

128

106

 

4x35

32.5

2870

1000

0.524

157

131

 

4x50

37.5

4000

1000

0.387

185

159

 

4x70

41.5

5150

1000

0.268

228

202

 

4x95

48.0

7050

1000

0.193

275

244

 

4x120

52.5

8450

500

0.124

313

282

 

4x150

57.0

10050

500

0.153

353

324

 

4x185

63.0

12150

500

0.0991

399

371

 

4x240

70.5

15300

500

0.0754

464

436

 

4x300

79.0

18700

250

0.0601

524

481

 

4x400

90.0

25000

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, RSW Armored, Multi Core (4) LV Cables.