Product Detail

0.6/ 1kV PVC Insulated, Single Core Cables with Copper Conductor

Code

YVV-U, YVV-R, CU/PVC/PVC, NYY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

(Max. 5 sec.)

Cross section 300 mm2

:

160 oC

Cross Section > 300 mm2

:

140 oC

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

 

1x1,5

5.8

50

1000

12.1

-

30

25

20

 

1x2,5

6.2

60

1000

7.41

-

39

34

27

 

1x4

7.0

85

1000

4.61

-

50

45

37

 

1x6

7.5

105

1000

3.08

-

62

57

48

 

1x10

9.0

160

1000

1.83

-

83

78

66

 

1x16

10.0

215

1000

1.15

127

107

103

89

 

1x25

11.5

320

1000

0.727

163

137

137

118

 

1x35

12.5

420

1000

0.524

195

165

169

145

 

1x50

14.0

570

1000

0.387

230

195

206

176

 

1x70

15.5

780

1000

0.268

282

239

261

224

 

1x95

18.0

1050

1000

0.193

336

287

321

271

 

1x120

19.5

1300

1000

0.153

382

326

374

314

 

1x150

21.0

1600

1000

0.124

428

366

428

361

 

1x185

23.5

1950

1000

0.0991

483

414

494

412

 

1x240

27.0

2550

1000

0.0754

561

481

590

484

 

1x300

30.5

3150

1000

0.0601

632

542

678

549

 

1x400

34.0

4200

1000

0.0470

730

624

817

657

 

1x500

37.0

5200

1000

0.0366

823

698

940

749

 

1x630

42.0

6450

500

0.0283

866

775

1042

858

 

               

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, PVC Insulated, Single Core LV Cables.