Product Detail
0.6/ 1kV PVC Insulated, Single Core Cables with Copper Conductor
Code YVV-U, YVV-R, CU/PVC/PVC, NYY U: Solid Conductor R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603 |
Application Indoor, outdoor or
underground; in cable ducts, at power or switching stations, local energy
distribution networks, industrial plants, and at places where there is no
risk of mechanical damage. Construction 1. Solid or stranded
copper conductors 2. PVC insulation 3. PVC outer
jacket |
|||||||||||
Technical
Data |
|
|
||||||||||
Max. operating temperature |
: |
70 oC |
||||||||||
Max. short circuit temperature |
: |
(Max. 5
sec.) |
||||||||||
Cross section ≤ 300 mm2 |
: |
160 oC |
||||||||||
Cross Section >
300 mm2 |
: |
140 oC |
||||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||||
Min. bending radius |
: |
12 x D |
||||||||||
(D: Cable outer diameter) |
||||||||||||
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|
||||||||||
Nominal |
Overall |
|
|
DC Conductor |
Current Carrying Capacity (A) |
|
||||||
Cross- |
Diameter |
Net Weight |
Delivery |
Resistance at |
In Ground at |
In Air at |
|
|||||
Section |
(approx.) |
(approx.) |
Length |
200C Max |
200C |
300C |
|
|||||
mm2 |
mm |
kg/km |
m |
Ohm/km |
*** |
*** |
*** |
*** |
|
|||
1x1,5 |
5.8 |
50 |
1000 |
12.1 |
- |
30 |
25 |
20 |
|
|||
1x2,5 |
6.2 |
60 |
1000 |
7.41 |
- |
39 |
34 |
27 |
|
|||
1x4 |
7.0 |
85 |
1000 |
4.61 |
- |
50 |
45 |
37 |
|
|||
1x6 |
7.5 |
105 |
1000 |
3.08 |
- |
62 |
57 |
48 |
|
|||
1x10 |
9.0 |
160 |
1000 |
1.83 |
- |
83 |
78 |
66 |
|
|||
1x16 |
10.0 |
215 |
1000 |
1.15 |
127 |
107 |
103 |
89 |
|
|||
1x25 |
11.5 |
320 |
1000 |
0.727 |
163 |
137 |
137 |
118 |
|
|||
1x35 |
12.5 |
420 |
1000 |
0.524 |
195 |
165 |
169 |
145 |
|
|||
1x50 |
14.0 |
570 |
1000 |
0.387 |
230 |
195 |
206 |
176 |
|
|||
1x70 |
15.5 |
780 |
1000 |
0.268 |
282 |
239 |
261 |
224 |
|
|||
1x95 |
18.0 |
1050 |
1000 |
0.193 |
336 |
287 |
321 |
271 |
|
|||
1x120 |
19.5 |
1300 |
1000 |
0.153 |
382 |
326 |
374 |
314 |
|
|||
1x150 |
21.0 |
1600 |
1000 |
0.124 |
428 |
366 |
428 |
361 |
|
|||
1x185 |
23.5 |
1950 |
1000 |
0.0991 |
483 |
414 |
494 |
412 |
|
|||
1x240 |
27.0 |
2550 |
1000 |
0.0754 |
561 |
481 |
590 |
484 |
|
|||
1x300 |
30.5 |
3150 |
1000 |
0.0601 |
632 |
542 |
678 |
549 |
|
|||
1x400 |
34.0 |
4200 |
1000 |
0.0470 |
730 |
624 |
817 |
657 |
|
|||
1x500 |
37.0 |
5200 |
1000 |
0.0366 |
823 |
698 |
940 |
749 |
|
|||
1x630 |
42.0 |
6450 |
500 |
0.0283 |
866 |
775 |
1042 |
858 |
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground :
200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load
factor 0.7
In Air :
300C; load factor 1.0
*** :
Flat formation; clearance between cables in air = 1 x cable outer diameter; in
ground = 7cm
*** :
Trefoil formation
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, PVC Insulated, Single Core LV Cables.