Product Detail

12/20 kV or 12.7/22 kV XLPE Insulated, Three Core Cables with Copper Conductor

Code

YXC8V-R, N2XSEY, CU/XLPE/CTS//PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

12/20 kV

 

 

12.7/22 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

56.5

4150

1000

0.524

0.416

0.141

183

182

3x50/16

59.5

4850

1000

0.387

0.395

0.155

216

217

3x70/16

63.0

5800

500

0.268

0.373

0.172

264

269

3x95/16

67.0

6900

500

0.193

0.355

0.191

316

326

3x120/16

71.0

8000

500

0.153

0.340

0.209

360

377

3x150/25

74.5

9250

500

0.124

0.329

0.225

404

426

3x185/25

78.5

10650

250

0.0991

0.319

0.243

457

488

3x240/25

85.0

13000

250

0.0754

0.304

0.273

532

576

3x300/25

90.0

15250

250

0.0601

0.295

0.296

599

654

3x400/35

98.0

19100

250

0.0470

0.284

0.331

685

750

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources