Product Detail

3.6/6 kV XLPE Insulated, Three Core Cables with Copper Conductor

Code

YXC8V-R, N2XSEY, CU/XLPE/CTS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

3.6/6 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

42.0

2700

1000

0.524

0.352

0.229

176

171

3x50/16

45.0

3350

1000

0.387

0.336

0.255

208

196

3x70/16

48.5

4150

1000

0.268

0.318

0.288

255

249

3x95/16

53.0

5200

500

0.193

0.303

0.324

307

307

3x120/16

57.0

    6250

500

0.153

0.292

0.359

353

353

3x150/25

60.5

7350

500

0.124

0.284

0.388

396

406

3x185/25

64.5

8650

500

0.0991

0.276

0.424

447

464

3x240/25

71.0

10850

250

0.0754

0.267

0.469

523

548

3x300/25

77.5

   13200

250

0.0601

0.263

0.486

581

632

3x400/35

86.0

16900

250

0.0470

0.257

0.521

653

726

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

 

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, 3-Core MV Cables (3.6/6 kV).