Product Detail
0.6/ 1kV XLPE Insulated, Concentric Conductor Screen, Multi-Core Cables with Copper Conductor
Code YXCV-R, CU/XLPE/SC/PVC, N2XCY R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603 Technical
Data |
Application Characterized with low dielectric
loss. Used indoor installations; in cable ducts; outdoor and underground at power
stations; in industrial plants and switching stations as well as local supply
systems where high degree of protection is required. In case of mechanical
damage, screen prevents hazardous effects of power leakage over surrounding
area. Construction 1. Stranded
copper conductors 2. XLPE
insulation 3. Filler 4.
Concentric copper wire 5. Copper
tape as binder 6.
Polyester tape 7. PVC outer
jacket |
|||||||||
Max. operating temperature |
: |
90 oC |
||||||||
Max. short circuit
temperature |
: |
250 oC (Max. 5
sec.) |
||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||
Min. bending radius |
: |
15 x D |
||||||||
(D: Cable outer diameter) |
||||||||||
|
||||||||||
|
||||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
|
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
|
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|
|||
3x25/16 |
24.5 |
1300 |
1000 |
0.727 |
143 |
130 |
|
|||
3x35/16 |
26.5 |
1600 |
1000 |
0.524 |
173 |
160 |
|
|||
3x50/25 |
29.0 |
2100 |
1000 |
0.387 |
205 |
195 |
|
|||
3x70/35 |
34.0 |
3000 |
1000 |
0.268 |
252 |
247 |
|
|||
3x95/50 |
39.0 |
4100 |
1000 |
0.193 |
303 |
305 |
|
|||
3x120/70 |
43.0 |
5100 |
500 |
0.153 |
346 |
355 |
|
|||
3x150/70 |
47.5 |
6200 |
500 |
0.124 |
390 |
407 |
|
|||
3x185/95 |
53.0 |
7700 |
500 |
0.0991 |
441 |
469 |
|
|||
3x240/120 |
59.5 |
10000 |
250 |
0.0754 |
511 |
551 |
|
|||
3x300/150 |
65.0 |
12300 |
250 |
0.0601 |
580 |
638 |
|
|||
3x400/185 |
73.0 |
15800 |
250 |
0.0470 |
663 |
746 |
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated, CC Screen, Multi Core (3) LV Cables.