Product Detail
0.6/ 1kV XLPE Insulated, Concentric Conductor Screen, Single Core Cables with Copper Conductor
Code YXCV-U, YXCV-R, CU/XLPE/SC/PVC, N2XCY U: Solid Conductor R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603 |
Application Characterized with low dielectric
loss. Used indoor installations; in cable ducts; outdoor and underground at power
stations; in industrial plants and switching stations as well as local supply
systems where high degree of protection is required. In case of mechanical
damage, screen prevents hazardous effects of power leakage over surrounding
area. Construction 1. Solid
or stranded copper conductors 2. XLPE
insulation 3. Filler 4.
Concentric copper wire 5. Copper
tape as binder 6.
Polyester tape 7. PVC
outer jacket |
||||||||||
Technical
Data |
|
|
|||||||||
Max. operating temperature |
: |
90 oC |
|||||||||
Max. short circuit
temperature |
: |
250 oC (Max. 5
sec.) |
|||||||||
Rated voltage |
: |
0.6 / 1kV |
|||||||||
Min. bending radius |
: |
15 x D |
|||||||||
(D: Cable outer diameter) |
|
|
|||||||||
|
|
|
|||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity (A) |
||||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|||||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|||||
mm2 |
mm |
kg/km |
m |
Ohm/km |
*** |
*** |
*** |
*** |
|||
1x1,5/1,5 |
10.5 |
140 |
1000 |
12.1 |
39 |
32 |
32 |
25 |
|||
1x2,5/2,5 |
11.0 |
160 |
1000 |
7.41 |
51 |
43 |
42 |
34 |
|||
1x4/4 |
11.3 |
200 |
1000 |
4.61 |
66 |
55 |
56 |
44 |
|||
1x6/6 |
11.5 |
220 |
1000 |
3.08 |
82 |
68 |
71 |
57 |
|||
1x10/10 |
12.5 |
390 |
1000 |
1.83 |
109 |
90 |
96 |
77 |
|||
1x16/16 |
14.0 |
430 |
1000 |
1.15 |
139 |
115 |
128 |
102 |
|||
1x25/16 |
15.5 |
550 |
1000 |
0.727 |
179 |
149 |
173 |
139 |
|||
1x35/16 |
16.5 |
650 |
1000 |
0.524 |
213 |
178 |
212 |
170 |
|||
1x50/25 |
18.0 |
850 |
1000 |
0.387 |
251 |
211 |
258 |
208 |
|||
1x70/35 |
20.0 |
1200 |
1000 |
0.268 |
307 |
259 |
328 |
265 |
|||
1x95/50 |
22.5 |
1600 |
1000 |
0.193 |
366 |
310 |
404 |
326 |
|||
1x120/70 |
25.0 |
2000 |
1000 |
0.153 |
416 |
352 |
471 |
381 |
|||
1x150/70 |
26.5 |
2300 |
1000 |
0.124 |
465 |
396 |
541 |
438 |
|||
1x185/95 |
29.0 |
2900 |
1000 |
0.0991 |
526 |
449 |
626 |
507 |
|||
1x240/120 |
32.0 |
3700 |
1000 |
0.0754 |
610 |
521 |
749 |
606 |
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
*** : Flat formation;
clearance between cables in air = 1 x cable outer diameter; in ground = 7cm
*** : Trefoil formation
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated, CC Screen, Single Core LV Cables.