Product Detail

0.6/ 1kV XLPE Insulated, Concentric Conductor Screen, Single Core Cables with Copper Conductor

Code

YXCV-U, YXCV-R, CU/XLPE/SC/PVC, N2XCY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Characterized with low dielectric loss. Used indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations as well as local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Solid or stranded copper conductors

2. XLPE insulation

3. Filler

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

 

 

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

1x1,5/1,5

10.5

140

1000

12.1

39

32

32

25

1x2,5/2,5

11.0

160

1000

7.41

51

43

42

34

1x4/4

11.3

200

1000

4.61

66

55

56

44

1x6/6

11.5

220

1000

3.08

82

68

71

57

1x10/10

12.5

390

1000

1.83

109

90

96

77

1x16/16

14.0

430

1000

1.15

139

115

128

102

1x25/16

15.5

550

1000

0.727

179

149

173

139

1x35/16

16.5

650

1000

0.524

213

178

212

170

1x50/25

18.0

850

1000

0.387

251

211

258

208

1x70/35

20.0

1200

1000

0.268

307

259

328

265

1x95/50

22.5

1600

1000

0.193

366

310

404

326

1x120/70

25.0

2000

1000

0.153

416

352

471

381

1x150/70

26.5

2300

1000

0.124

465

396

541

438

1x185/95

29.0

2900

1000

0.0991

526

449

626

507

1x240/120

32.0

3700

1000

0.0754

610

521

749

606

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1