Product Detail

0.6/ 1kV XLPE Insulated, Control Cables with Copper Conductor

Code

YXV-U, CU/XLPE/PVC, N2XY

U: Solid Conductor

Standards

IEC 60502-1, VDE 0271

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid copper conductors

2. XLPE insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

5x1,5

12.0

240

1000

12.1

21.0

18.0

6x1,5

13.0

250

1000

12.1

19.5

16.8

7x1,5

13.0

270

1000

12.1

18.0

15.6

8x1,5

15.0

340

1000

12.1

16.5

14.4

10x1,5

15.7

420

1000

12.1

15.0

13.2

12x1,5

15.7

450

1000

12.1

14.3

12.6

14x1,5

17.0

500

1000

12.1

13.5

12.0

16x1,5

17.5

550

1000

12.1

12.8

11.4

19x1,5

18.5

620

1000

12.1

12.0

10.8

21x1,5

20.5

680

1000

12.1

11.3

10.2

24x1,5

22.0

800

1000

12.1

10.5

9.6

27x1,5

22.5

850

1000

12.1

10.2

9.4

30x1,5

22.5

900

1000

12.1

9.9

9.1

37x1,5

25.0

1050

1000

12.1

9.3

8.6

40x1,5

26.0

1150

1000

12.1

9.0

8.4

48x1,5

28.0

1400

1000

12.1

8.4

7.9

52x1,5

29.0

1450

1000

12.1

7.8

7.4

61x1,5

31.0

1700

1000

12.1

7.5

7.2

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated Control Cables (1).