0.6/ 1kV XLPE Insulated, Control Cables with Copper Conductor

Code

YXV-U, YXV-R, CU/XLPE/PVC, N2XY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0271

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. XLPE insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

5x2,5

13.0

280

1000

7.41

28.0

24.0

6x2,5

14.0

330

1000

7.41

26.0

22.0

7x2,5

14.0

350

1000

7.41

24.0

21.0

8x2,5

15.0

450

1000

7.41

22.0

19.0

10x2,5

17.0

510

1000

7.41

20.0

17.5

12x2,5

17.5

570

1000

7.41

19.0

16.5

14x2,5

18.0

640

1000

7.41

18.0

16.0

16x2,5

19.0

720

1000

7.41

16.5

15.0

19x2,5

20.0

800

1000

7.41

16.0

14.5

21x2,5

20.5

870

1000

7.41

15.0

13.5

24x2,5

23.0

1040

1000

7.41

14.0

13.0

27x2,5

24.0

1100

1000

7.41

13.5

12.5

30x2,5

25.0

1200

1000

7.41

13.0

12.0

37x2,5

27.0

1450

1000

7.41

12.5

11.5

40x2,5

28.0

1550

1000

7.41

12.0

11.0

48x2,5

30.0

1900

1000

7.41

11.0

10.5

52x2,5

32.0

2050

1000

7.41

10.5

10.0

61x2,5

34.0

2300

1000

7.41

10.0

9.5

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1