Product Detail

5.8/10 kV (6/10 kV) or 6.35/11 kV XLPE Insulated, Double Steel Tape Armored, Three Core Cables with Copper Conductor

Code

YXC8VZ4V-R, N2XSEYBY, CU/XLPE/CTS/PVC/STA/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502 - 2, VDE 0276 – 620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. Inner sheath

9. Galvanized double steel tape

10. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

5.8/10 kV

 

 

6.35/11 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

51.5

3950

1000

0.524

0.374

0.189

178

173

3x50/16

54.5

4650

1000

0.387

0.355

0.209

210

206

3x70/16

58.5

5600

500

0.268

0.336

0.236

256

257

3x95/16

63.0

6800

500

0.193

0.320

0.263

307

313

3x120/16

67.0

7900

500

0.153

0.308

0.291

349

360

3x150/25

70.0

9100

500

0.124

0.299

0.314

392

410

3x185/25

74.0

10550

250

0.0991

0.290

0.341

443

469

3x240/25

81.5

13000

250

0.0754

0.278

0.387

513

553

3x300/25

88.0

15900

250

0.0601

0.270

0.422

576

635

3x400/35

96.0

19800

250

0.0470

0.261

0.475

650

731

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, DST Armored, 3-Core MV Cables (5.8/10 kV).